Autotrol Turbine Water Meter
|
| |
Product Information

1 TM-NPT shown
Flow Sensor Specifications
|
MODEL 1TM
1 inch (25 mm)
|
MODEL 2TM
2 inch (51 mm)
|
|
|
|
| Flow rate range |
0.25 40 gpm
(0.06 9.5 m3 /h) |
2 250 gpm
(0.45 60 m3/h) |
|
|
|
| Materials of construction: |
|
|
| Housing |
|
|
| Turbine (Impeller) |
30% Glass-Filled PPO* |
30% Glass Filled PPO* |
| Bearings |
Polypropylene |
Polypropylene |
| Shaft |
Polyimide |
Carbon Graphite |
|
302SS |
No shaftthrust bearing |
|
|
|
| Accuracy |
±3% of reading |
±3% of reading |
|
|
|
| Pressure Drop |
1.5 psi @ 30 gpm
(10.3 kPa @ 7 m3/h) |
2.5 psi @ 150 gpm
(17.2 kPa @ 34 m3/h) |
| Maximum water temp. |
100°F (38°C) |
100°F (38°C) |
| Maximum temp. |
122°F (50°C) |
122°F (50°C) |
| Maximum pressure |
127 psi (875 kPa) |
100 psi (689 kPa) |
| Available cable lengths |
5, 10, 20, 25, 50 ft
(1.5, 3.0, 6.1, 7.6, 15.2 m) |
5, 10, 20, 25, 50 ft
(1.5, 3.0, 6.1, 7.6, 15.2 m) |
| Maximum cable length kit form |
1,000 ft. (305 m) |
1,000 ft. (305 m) |
PPO Polyphenylene Oxide
NOTES:
- THE Autotrol® TURBINE WATER METERS ARE NOT TO BE USED AS A UNION
- MUST BE SUPPORTED AT BOTH ENDS
- Should be located in horizontal pipe WITH 18 inches of straight pipe on either side
- SHOULD HAVE FLOW oriented from bottom to top in vertical position
Ordering Information
| 1TM-ESW |
|
1 inch turbine meter with solvent weld PVC adapters |
| 1TM-NPT |
|
1 inch turbine meter with 1 inch NPT brass adapter |
| 2TM-ESW |
|
2 inch turbine meter with solvent weld PVC adapters |
| 2TM-NPT |
|
2 inch turbine meter with 2 inch NPT brass adapter |
| 400B418-701 |
|
1 inch turbine meter only |
| 480B78G1 |
|
2 inch turbine meter only |
| WATER METER CABLE (ORDER ONE CABLE FOR EACH TURBINE) |
| 49C25 |
|
25 ft cable with Hall Effect sensor |
| 49C50 |
|
50 ft cable with Hall Effect sensor |
| 49CKT |
|
25 ft cable with Hall Effect sensor and junction box |
|
|
|