Model 2430P Microprocessor-Based Conductivity and ORP Controllers
Product Information
LONWORKS* Technology is the latest in microprocessor capability that gives the user the highest level of application flexibility.
A large illuminated graphics screen, multiple inputs and very easy setup with easy field upgrade characterize this new technology.
The unit does not include plumbing or a sensor. For use with process-type conductivity sensors (order separately).
Features
- 4-electrode conductivity input includes fouling compensation and alarm.
- Differential ORP sensor input with diagnostics indicate fouled reference or open PT band.
- Input for flowswitch lockout.
- Two water meter inputs, MTR1 and MTR2.
- Conductivity Blowdown Relay options:
- Bleed x gallons for every x gallons makeup
- Bleed x minutes for every x gallons of makeup
- Bleed by setpoint
- Bleed by cycles of concentration with NCON/NCKT Option
- Bleed by multi-setpoint selected with NCON/NCKT Option
Three user-selectable relay options (four additional with NRLY):
- Feed by setpoint, direct or reverse;
- Water meter actuated feed. MTR1, MTR2 or sum;
- Feed after blowdown by percent of bleed time;
- Feed by percentage of time;
- Feed by schedule (-RTC Option);
- General alarm contact.
- View only
- Operator
- Technician
Four different languages.
- English Spanish (standard)
- English French (optional)
- English German(optional)
Specifications
| Inputs |
|
|
| Power |
|
80-300 VAC |
| Sensor |
|
2 or 4 electrode Conductivity and ORP glass Electrode w/BNC |
| Temperature comp. |
|
None, 500 NTC, 4K NTC, 10K NTC, 100 PTC, 1K PTC,
3K PTC and 10K PTC |
| Flow / level switch |
|
Dry contact |
| Water Meter Input |
|
Two contacting head or open collector |
|
|
|
| Outputs |
|
|
| Relays |
|
3 Amps @ 120 VAC |
| 4-20 mA |
|
Two, isolated w/-35L |
|
|
|
| Controller |
|
|
| Conductivity Range |
|
0-100,000 µS (varies with sensor) |
| Conductivity Accuracy |
|
±40 µS |
| Conductivity Resolution |
|
10 µS |
| ORP Range |
|
-1000 to +1000 mV |
| ORP Accuracy |
|
±5 mV |
| ORP Resolution |
|
1 mV |
| Deadband |
|
Adjustable |
| Setpoints |
|
Direct or Reverse (field configurable) |
| Feed timer |
|
Adjustable |
| Keypad |
|
Numeric |
| Display |
|
Illuminated 128 x 64 pixel LCD |
| Ambient Temperature |
|
32-158°F (0-70°C) |
| Enclosure |
|
ABS Plastic |
|
|
NEMA-4X Optional |
| 2430P |
|
LonWorks Technology-based controller with 4 selectable relays for HIGH/LOW setpoints or alarms. Requires ORP and conductivity sensor (530, 540, or 543) which must be ordered separately. Controller has no power cord, outlets or plumbing. |
| CONTROLLER OPTIONS (optional; select no more than three) |
| -RTC |
|
Schedule feed timer with 28-day programmable clock for selectable relays. |
| -35L |
|
Two 4-20 mA output configurable for remote data acquisition of ORP and conductivity. |
| -RS2L |
|
Communications node with the LRWS program; requires -RTC Option. |
| -NIN |
|
Network interface node; allows 1 NRLY and/or up to 3 NCON/NCKTs to be added. |
| ENCLOSURE OPTIONS (optional) |
| -DU |
|
Duplex outlet for chemical pump, power cord. |
| LANGUAGE OPTIONS (optional, choose one, English and Spanish Standard) |
| -EF |
|
English and French. |
| -EG |
|
English and German. |
| REMOTE NODE OPTIONS (optional; MUST purchase -NIN Option above) |
| NRLY |
|
Four additional relays with enclosure (1 per 2000 Series Controller). |
| NCON |
|
Conductivity node (node only). |
| MOUNTING OPTIONS |
| PM |
|
Panel mount 6¼ inch square cutout. |
| BM |
|
Bracket for pipe mounting. |
| SOFTWARE AND EXTERNAL MODEMS |
| LRWS |
|
Windows-based software for computer to communicate with 2000 Series Controllers. |
| MD4X |
|
High-Baud modem in NEMA-4X enclosure ready to power. |
| MD |
|
High-Baud modem for use with 2000 Series Controllers. |
* LONWORKS is a registered trademark of Echelon Corporation.
|