Conductivity,ORP,Controller,Model 2430P,Lakewood,Instruments

Conductivity ORP Controller Model 2430P from Lakewood Instruments


 

Model 2430P Microprocessor-Based Conductivity and ORP Controllers

Conductivity,ORP,Controller,Model 2430P,Lakewood,InstrumentsLONWORKS* Technology is the latest in microprocessor capability that gives the user the highest level of application flexibility.

A large illuminated graphics screen, multiple inputs and very easy setup with easy field upgrade characterize this new technology.

The unit does not include plumbing or a sensor. For use with process-type conductivity sensors (order separately).

Features
  • 4-electrode conductivity input includes fouling compensation and alarm.
  • Differential ORP sensor input with diagnostics indicate fouled reference or open PT band.
  • Input for flowswitch lockout.
  • Two water meter inputs, MTR1 and MTR2.
  • Conductivity Blowdown Relay options:
  • Bleed x gallons for every x gallons makeup
  • Bleed x minutes for every x gallons of makeup
  • Bleed by setpoint
  • Bleed by cycles of concentration with NCON/NCKT Option
  • Bleed by multi-setpoint selected with NCON/NCKT Option
  • Three user-selectable relay options (four additional with NRLY):
    • Feed by setpoint, direct or reverse;
    • Water meter actuated feed. MTR1, MTR2 or sum;
    • Feed after blowdown by percent of bleed time;
    • Feed by percentage of time;
    • Feed by schedule (-RTC Option);
    • General alarm contact.
    • Three security levels:
    • View only
    • Operator
    • Technician
  • Four different languages.
    • English Spanish (standard)
    • English French (optional)
    • English German(optional)
    Specifications

    Inputs
    Power 80-300 VAC
    Sensor 2 or 4 electrode Conductivity and ORP glass Electrode w/BNC
    Temperature comp. None, 500 NTC, 4K NTC, 10K NTC, 100 PTC, 1K PTC,
    3K PTC and 10K PTC
    Flow / level switch Dry contact
    Water Meter Input Two contacting head or open collector
    Outputs
    Relays 3 Amps @ 120 VAC
    4-20 mA Two, isolated w/-35L
    Controller
    Conductivity Range 0-100,000 S (varies with sensor)
    Conductivity Accuracy 40 S
    Conductivity Resolution 10 S
    ORP Range -1000 to +1000 mV
    ORP Accuracy 5 mV
    ORP Resolution 1 mV
    Deadband Adjustable
    Setpoints Direct or Reverse (field configurable)
    Feed timer Adjustable
    Keypad Numeric
    Display Illuminated 128 x 64 pixel LCD
    Ambient Temperature 32-158F (0-70C)
    Enclosure ABS Plastic
    NEMA-4X Optional

    2430P   LonWorks Technology-based controller with 4 selectable relays for HIGH/LOW setpoints or alarms. Requires ORP and conductivity sensor (530, 540, or 543) which must be ordered separately. Controller has no power cord, outlets or plumbing.
    CONTROLLER OPTIONS (optional; select no more than three)
    -RTC   Schedule feed timer with 28-day programmable clock for selectable relays.
    -35L   Two 4-20 mA output configurable for remote data acquisition of ORP and conductivity.
    -RS2L   Communications node with the LRWS program; requires -RTC Option.
    -NIN   Network interface node; allows 1 NRLY and/or up to 3 NCON/NCKT’s to be added.
    ENCLOSURE OPTIONS (optional)
    -DU   Duplex outlet for chemical pump, power cord.
    LANGUAGE OPTIONS (optional, choose one, English and Spanish Standard)
    -EF   English and French.
    -EG   English and German.
    REMOTE NODE OPTIONS (optional; MUST purchase -NIN Option above)
    NRLY   Four additional relays with enclosure (1 per 2000 Series Controller).
    NCON   Conductivity node (node only).
    MOUNTING OPTIONS
    PM   Panel mount 6 inch square cutout.
    BM   Bracket for pipe mounting.
    SOFTWARE AND EXTERNAL MODEMS
    LRWS   Windows-based software for computer to communicate with 2000 Series Controllers.
    MD4X   High-Baud modem in NEMA-4X enclosure ready to power.
    MD   High-Baud modem for use with 2000 Series Controllers.

    * LONWORKS is a registered trademark of Echelon Corporation.