orp,conductivity,cooling,tower,controller,model,2430,lakewood,instruments

ORP and Conductivity Cooling Tower Controller Model 2430



ORP and Conductivity Cooling Tower Controller Model 2430

 
Model 2430 Microprocessor-Based ORP & Conductivity Cooling Tower Controllers

Product Information

LONWORKS® Technology is the latest in microprocessor capability that gives the user the highest level of application flexibility. A large graphic screen, multiple inputs and very easy setup with easy field upgrade characterize this new technology.

* LONWORKS is a registered trademark of Echelon Corporation.

Benefits
  • Multiple control options in a single economical package.
  • Very accurate control of chemical feed and cycles of concentration.
  • Very low maintenance.
  • Tolerant to power surges and brownouts.
  • Power cord, plug outlets and attached plumbing make installation easy. There is plenty of protected room inside the enclosure for electrician wiring.
  • Very accurate monitoring of the evaporated water.
  • Feeds chemical AFTER blowdown.
  • Has expansion slots to add additional control, such as chiller loop monitor and cycles of concentration based on incoming makeup water.
Features
  • 4-electrode conductivity includes fouling compensation and alarm.
  • Differential ORP sensor with diagnostics indicate fouled reference or open pt band.
  • Integral flowsight & flowswitch lockout.
  • Records both makeup (MTR1) and blowdown (MTR2) water meter total gallons.
  • Configure blowdown water meter (MTR2) as second makeup meter.
  • Blowdown Relay options:
  • Bleed x gallons for every x gallons makeup
  • Bleed x minutes for every x gallons of makeup
  • Bleed by setpoint
  • Bleed by cycles of concentration with NCON/NCKT Option
  • Bleed by multi-setpoint selected with NCON/NCKT Option
  • Three user-selectable relay options (four additional with NRLY):
    • Feed by setpoint, direct or reverse;
    • Water meter actuated feed. MTR1, MTR2 or sum;
    • Feed after blowdown by percent of bleed time;
    • Feed by percentage of time;
    • Schedule feed timer (-RTC Option);
    • General alarm contact.
    • Three security levels:
    • View only
    • Operator
    • Technician
  • Four different languages.
    • English Spanish (standard)
    • English French (optional)
    • English German (optional)
    Specifications
    Inputs
    Power 80-300 VAC
    Sensor 4 electrode Conductivity
    ORP combination glass electrode
    Temperature comp. Automatic
    Flow switch Dry contact
    Water Meter Input Two contacting head or open collector
    Outputs
    Relays Four, 3 Amps @ 120 VAC
    4-20 mA Two, isolated w/-35L
    Sensor/Plumbing
    Pressure 140 psi (9.7 bar) @ 100°F (38° C)
    Max. Temperature 140°F (60° C)
    Min. Flow 1 gpm (3.8 Lpm)
    Controller
    Conductivity Range 0-5,000 m S (other ranges optional)
    Conductivity Accuracy ±40 µS
    Conductivity Resolution 10 µS
    ORP Range -1000 to +1000 mV
    ORP Accuracy ±5 mV
    ORP Resolution 1 mV
    Deadband Adjustable
    Setpoints Direct or Reverse (configurable in the field)
    Feed timer Adjustable
    Keypad Numeric
    Display Illumin. 128x64 pixel LCD
    Ambient Temperature 32-158° F (0-70° C)
    Enclosure Rating ABS Plastic
    NEMA 4X Optional

    Ordering Information
    2430   LONWORKS Technology-based ORP and conductivity controller with plumbing and flow switches. Four relays are integral to the system. One is dedicated to blowdown. The others may be configured for ORP, inhibitor feed on conductivity, water meter, percent of time or schedule feed. ORP range is -1000 to +1000 mV and conductivity range is 0-5,000 µS.
    CONTROLLER OPTIONS (optional, select no more than three)
    -RTC   Adds 24-hour clock and calendar to controller (required to configure relays to feed chemicals/biocides based on time of day and for data acquisition if using the -RS2L Option). NOTE: ADDING AN -RTC CARD DOES NOT ADD RELAYS.
    -35L   Two 4-20 mA outputs configurable for remote data acquisition of conductivity and ORP.
    -RS2L   Communications node with shareware software. Requires -RTC Option.
    -NIN   Network interface node. Allows 1 NRLY and/or up to 3 NCON/NCKT to be added.
    ENCLOSURE OPTIONS (optional)
    -WP   Weatherproof and watertight. ½ inch knockouts. No outlets or power cords.
    LANGUAGE OPTIONS (optional, choose one, English and Spanish Standard)
    -EF   English and French.
    -EG   English and German.
    REMOTE NODE OPTIONS (optional, MUST purchase -NIN Option above)
    NRLY   Four additional relays with enclosure (1 per 2000 Series Controller).
    NCON   Conductivity node for makeup water or closed loop control (node only).
    NCKT   Conductivity node for makeup water or closed loop control with PVC sensor, tee and enclosure. Maximum water pressure and temperature is 140 psi @ 100°F (9.7 bar @ 38°C).
    SOFTWARE AND EXTERNAL MODEMS
    LRWS   Windows-based registered software for computer to communicate with 2000 Series Controllers.
    MD4X   High-Baud modem in NEMA 4X enclosure ready to power.
    MD   High-Baud modem for use with 2000 Series Controllers.

    Site Designed And Maintained By Panther Marketing & Design